Per 100 sq ft of wall or partition area with no opening exceeding 22 0 sq in.
Cut in boxes in fire rated walls.
Boxes are suitable for installation in staggered stud wall configuration.
Fire rated one and two hours 1.
See carlon s ner 140 report or the ul fire resistance directory which describes in detail the use of zip boxes in these assemblies.
Clearance between boxes and cut outs in wall shall not exceed 1 8 in.
At that point put on the fire pad then have the wall closed up.
These materials are found under cliv in the fire resistance directory published by ul.
Cut opening in wall with care to ensure neat fi t of the wall box 4.
All boxes must also have more than 24 inches of horizontal spacing between outlets on either side of the fire rated wall.
Use the actual wall box as a cut out template whilst referring to the table above for recommended cut out dimensions 3.
If required remove knockout from wall box for suitable cable entry 5.
If it s a fire rated existing wall you will have to cut it open to mount your box to the framing and then have it patched.
Generally the spacing between boxes cannot be less than 24 inches but closer spacing is permitted where wall opening protective materials are installed according to the requirements of their classification.
This means that on 24 oc studs outlets must be placed at least one stud cavity away both sides of wall.
In within a rated wall assembly as long as the sum total area of openings wall cutouts for those boxes does not exceed 100 square inches for any 100 sq.
Ceiling boxes and single gang outlet switch boxes may be used in a 2 hour or less fire rated floor ceiling assembly.
Used in both 2 and 1 hour fire rated wall assemblies.
Metallic outlet boxes qcit for use in fire resistant rated assemblies all ul listed single and double gang metallic outlet and switch boxes with metallic or nonmetallic cover plates may be installed in bearing and nonbearing wood stud and steel stud walls with fire rating not exceeding 2 hours.
That s about as untrue as can be.
Outlet and switch boxes on opposite sides of a wall or partition within the same stud cavity shall be separated by a horizontal distance of not less than 3 in.